High Voltage Electrical Power Distribution Rmu Incomer and Outgoing Cabinet
- Certification
- CCC, ISO9001
- Installation
- Fixed
- Structure
- Cabinet
- Shell Material
- Stainless Steel
- Voltage Level
- High Voltage
- Current
- AC
Technical Specifications
No. | Item | Unit | Data |
1 | Rated voltage | kV | 24 |
2 | Rated Current | A | 630 |
3 | Rated Frequency | Hz | 50/60 |
4 | Rated short circuit current | kA | 20 |
5 | Rated short time withstand current(3s) | kA | 20 |
6 | Rated peak withstand current | kA | 50 |
7 | Rated power frequency withstand voltage | kV | 65/79 |
8 | Rated lightning impluse withstand voltage | kV | 125/145 |
9 | Secondary loop 1 min power frequency withstand voltage | kV | 2 |
Environmental Conditions
1. Ambient temperature: not higher than +40 ºC, not less than -15 ºC (at -30 ºC to allow storage and transportation).
2. Altitude: not exceed 1000m.
3. Earthquake intensity: not more than 8 degree.
4. Wind pressure:≤700pa
5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration