27kV Auto Recloser

Transport Package
Wooden Case
Pole
3poles
Function
Overcurrent Protection
Max. Current
800A
Max. Voltage
27kv
Contact Now

Description

 

Rcw+ type 27kV auto circuit recloser is designed for using voltage rating up to maximum 30kV level system.In order to provide with a high reliable equipments, Beierbian team increased the whole design schemas as below.

---------------------------------------------------

Rcw+ type 27kV auto circuit recloser is ANSI/IEC standardized plus design products which is equipped with one magnetic actuator mechanism, one manual closing/opening/Locking device, 3 current sensors, max 6 voltage sensors, with more functional like protection curves + curves programble, coodination logics + logics  programble,  programble communication protocols, PC software, APP control tool, etc...  with RWK352 controller,....

---------------------------------------------------

Rcw+ type 27kV auto circuit recloser is a solid insulation reclosure with zero pressure Sf6 GAS sealed. with high creepage design, higher insulation level,  suit using for Maximum 30kV level sytem.

It's vacuum interrupting technology, and IP67 IP protection class, It avoid any bad influence high polution enviroment of humidity, salt or alkali incursion or small animal,etc...

---------------------------------------------------

Rcw+ type 27kV auto circuit recloser is proper for using in either important area or extreme bad envirment area which normal ACR is not capable well service!

Feature of 27kV auto circuit recloser

● Service environment

Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃

Humidity: Monthly average humidity 95%; Daily average humidity 90% .

Altitude above sea level: Maximum installation altitude: 2500m or more higher.

Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake

●Offering With optional classes for rated current range:

--Type RCW27, Rating22-27 kV with 630A, 16 kA up to 1250A, 20kA;

With optional classes for different grid application installation: Single phase & Three phase.

With optional relay protection& logics for user choice:

+Instantaneous over-current protection.

+Timing over-current protection

+Negative sequence over-current protection.

+Directional over-current protection(*).

+Over-voltage protection./Under voltage protection.

+Programable protection relay curves total 10 nos ANSI/IEC curves.

+Cold load pickup protection TCC +Hot line tag

+Earth protection EF/SEF +Zone Sequence Co-ordination

+More relay functions can be customized.

With optional communication protocols & I/O port for user choice:

36kV auto recloser controller

RS-232 and RS-485 ports supporting.

DNP3.0 communication protocol support(*).

Modbus communication protocol is optional(*).

IEC 60870-5-101 communication protocol support.

IEC 60870-5-104 communication protocol support.(*). 

IEC 61850 communication protocol support.(*). 

The recloser can communicate through GPRS(Or GSM) modem with English or Specified language (*).

With optional functions for user.

Rated currents, System phase current.

Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh),

reactive power(kV arh), power factor .

With optional reclosing interval for user pre-program:

Reclosing times setting support.

Dead time setting support.

With events recording function:

SOE 10000 operations record.

Fault record and normal operation record.

Note: (*) mean should customized by manufacturer if needed.

●Time-Overcurrent Curves The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent

elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time

Characteristic Equations for Overcurrent Relays.

IEC Curves:  
36kv auto recloser IEC curve C1 (Standard Inverse)
C2 (Very Inverse)
C3 (Extremely Inverse)
C4 (Long-Time Inverse)
C5 (Short-Time Inverse)
U.S. Curves:  
36kv auto recloser IEEE curve U1 (Moderately Inverse)
U2 (Inverse)
U3 (Very Inverse)
U4 (Extremely Inverse)
U5 (Short-Time Inverse)

● PC software for controller Testing, Setting, programing, Update.

36kv auto recloser parameter setting software

Human friendship interface                                               Programmable Time-Overcurrent curve

36kv auto recloser programble software

● Recloser feature a)Outline of recloser:

The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

b)The recloser tank feature:

The Vacuum recloser tanks are manufactured from 304# grade stainless steel and are powder coated a light grey colour. Whole recloser IP67 protection class, equipped with a auxiliary plug to connect with recloser controller by control cable, Diameter Max22mm, 6 M length (8M for special).

It’s can performance serve more than 20 years long term under heavy duty circumstance.

● Main new advantages of RCW

36kv auto recloser switch tank

Visible ON/OFF indicatorIP67 class waterproof plug connector

1.Apply ANSOFT design the high performance magnetic actuator,high reliable and free maintenance
2.Manual closing device
3.Automatic Blocking Device for Manual opening
4.Mechanical locking device
5.Electronic locking device
6.Mechanical counter
7.Electronic counter
8.Visble on the ground reflector material mechanical open/closer indicator
9.IP67 inflatable tank SF6 Gas insulation,Pneumatic value,barometer
10.Integral type tank .Lifting lug, Earthing bolt
Note:The above parts are optional devices.Please provide requirement before placing an orde

 

Primacy incomer terminal (directly connect to interrupter reduce power lost) Current sensor (external modular design easy for quality control and maintenance) Accuracy: ±0.5% Ratio:800/1 36kv auto recloser embedded pole Vacuum interrupter(Adopt the APG technology,increasing the whole insulation and weathering performance)
Internal Voltage sensors incorporated within the vacuum interrupter module It's equipped with two voltage sensors,one for measuring the voltage of incoming side,and another one for measuring the voltage of outgoing side.

27kV Auto Recloser

36kv auto recloser epoxy resin pole

shielded 4-conductor cable connection  Accuracy:±0.2% Voltage Sensor  Ratio:500/1 or 1000/1

●Accessories of RCW

All above insulating components for BIL 200kV expanding using. Any question please contact with our engineer.

27kV Auto Recloser

Upper voltage shield 3 pcs/set

Standard made of T2 copper material, for 630/1250A rated current using. With  expanding range.

27kV Auto Recloser

Terminal 6 pcs/set
 

Mobile APP software of 15kV auto recloser

Map guide&location Monitoring&Controlling

36kV auto recloser software 36kV auto recloser login software

Setting & Modification Event Records

36kV auto recloser setting software 36kV auto recloser event report software

●Master software for Distribution Automation Management

36kV auto recloser software map

36kV auto recloser automation system SLD

Specification of 27kV auto recloser

N Item Unit Data
1 Rated max voltage kV - - 27 -
2 Rated current A 630/800/1250
3 Rated frequency HZ 50/60
4 Power frequency 1min Dry kV - 55 - -
Wet - 45 - -
5 Lightning impulse withstand voltage(peak) kV - 95/100* - -
6 Rated short circuit breaking current kA 12.5/16/20/25*
7 Rated short current switching current(peak) kA 31.5/40/50/63*
8 Rated peak value withstand current kA 31.5/40/50/63*
9 4S short time withstand current kA 12.5/16/20/25*
11 Rated operating circulate   O-0.5S-CO-2S-CO-2S-CO
10 Breaking current frequency under rated short circuit time 200
12 Mechanism life time 10000
13 Secondary loop 1 min power frequency withstand kV 2
14 Auxiliary voltage supply Vac 220±20%
15 Battery bank Vdc 12×2
16 Capacitor unit Vdc 220